PR-18DC-DA-R CPU Units ( Expandable & With Keypad LCD)
PR-18DC-DA-R CPU Units ( Expandable & With Keypad LCD)
PR-18DC-DA-R CPU Units ( Expandable & With Keypad LCD)
PR-18DC-DA-R CPU Units ( Expandable & With Keypad LCD)
PR-18DC-DA-R CPU Units ( Expandable & With Keypad LCD)
PR-18DC-DA-R CPU Units ( Expandable & With Keypad LCD)

◆70 ready-to use functions integrated-no additional devices such as operating hours counter required. 

◆Extremely large program capacity:up to 1024 functions possible.

◆12 digital inputs(incl 6AI with 12/24V DC)and 6 digital outputs on board. 

◆Flexibly expandable up to 140DI,134DO,72AI,and 32AO.

FEATURES

Timers : 1024

Counters :1024

Function Blocks : 1024

Operation temp. : -20℃-55℃ 

Storage :-40℃-70℃

Protection : IP20(Non-waterproof) 

SEND US YOUR MESSAGE
Video
Product Description

 

Highlight of PR-18 Series

◆70 ready-to use functions integrated-no additional devices such as operating hours counter required. 

◆Extremely large program capacity:up to 1024 functions possible.

◆12 digital inputs(incl 6AI with 12/24V DC)and 6 digital outputs on board. 

◆Flexibly expandable up to 140DI,134DO,72AI,and 32AO.

◆Display of message texts,actual and set-point values and direct modification of the values on the display(not on pure variants).

◆Integrated data retentivity-ensures backup of the current values in the event of a power failure.

◆Customizable Start-up page/screen.

◆Bool function,multiple timers,counters,PWM,PI controller,Ramp.Analog math supported. 

◆Can be modularly expanded up to 274 I/Os.  

◆230V units can be expanded with analog modules. 

◆Data-logging:Data from the production process can be saves in SD card of the external accessory called ELC-MEMORY to either read it with a PC or evaluate it from the SD card at the workstation.

◆Extremely simple software

◆Display of up to 128 messages.

◆Multiple kinds of registers can be accessed.

◆Parameters setting menu in LCD panel.

◆Parameters can be modified in the alarming message.

◆Modbus RTU/ASCII protocol supported.

◆Retentive memory capability.

◆Powerful communication capability(1RS232 port,1 RS485 port and 1 expansion port)

◆Password protection.

◆It’s optional for xLogic to act as salve or master in certain Modbus communication network.

◆Backup at Real Time Clock(RTC) at 25 ℃: 20 days.

◆Communicate with third party device which supports Modbus network.

 

 

Model Selector

 

PR-18 Series CPU
Model Supply volt Inputs Outputs High-speed count PWM HMI RTC G.W(g)
PR-18AC-R AC110~
240V
12 Digital 6relays
(10A)
 None NO YES YES 400g
PR-18DC-DA-R DC12V-DC24V 6 digital
/analog
+6 digital
6 relays
(10A)
 4 routes NO YES YES 400g
 
PR-18DC-DA-RT DC12V-DC24V 6 digital
/analog
+6 digital
4 relays
(10A)+2 transistor(0.3A)
4 routes YES YES YES 400g

 

 

Technical Specifications

 

GENERAL SPECIFICATIONS

Timers  : 1024

Counters  :1024

Function Blocks : 1024

Operation temp. : -20℃-55℃ 

Storage :-40℃-70℃

Protection : IP20(Non-waterproof) 

RTC accuracy : MAX ±2S/day

RTC Backup at 25 °C : 20 days

Program and settings Backup :10 years

Data Power-off retentivity : 10 years

Modify parameters via keypad LCD:  yes

Dimensions : 95*90*55(Unit:mm)

Certificate : CE

Installation : 35mm-DIN rail or screw for installation

Expansion capacity: 16 modules (PR-E-16)

Password protection : 4-digit number password protection or disable program upload function

Communication interface : TTL interface , 1 RS232 port & 1 RS485 port

Communication protocol : Modbus RTU/ASCII

 



Technical Index

Power supply:
Nominal voltage DC 12-24V
Operating limits  DC 10.8-28.8V
Immunity from micro power cuts  Typ.5 ms 
Max. Startup current Max. 0.25A
Max. absorbed power 3.5 W (10.8V dc) ; 4 W (28.8V dc)
Protection against polarity inversions Yes
Input parameters:
Input No 12 ( I1-IC )
Digital input  12 ( I1-IC )
Analogue input  6 ( I1-I6)(0..10V DC) 
Digital inputs( I7-IC ) 
Input voltage  DC0-28.8V
Input signal0  < 5V DC; <1mA
Input signal1  > 8 V DC;>1.7mA
Input current 2.3mA @ 10.8V dc
2.6mA @ 12.0 V dc
5.2 mA @ 24 V dc
6.3 mA @ 28.8 V dc
Response time  0 to 1 :<1 ms ;1 to 0 :<1 ms
Maximum counting frequency 60k Hz(I9--IC)
Sensor type Contact or 3-wire PNP
Input type Resistive
Isolation between power supply and inputs None
Isolation between inputs None
Inputs used as digital inputs( I1-I6 )
Input voltage  DC0-28.8V
Input signal0  < 5V DC;<0.1mA
Input signal1  > 8 V DC;>0.3mA
Input current  0.4mA @ 10.8V dc
0.5mA @ 12.0 V dc
1.2mA @ 24 V dc
1.5mA @ 28.8 V dc
Response time  0 to 1 :Typ. 1.5 ms ;1 to 0 :Typ. 1.5 ms
Maximum counting frequency Typ.:4 HZ
Sensor type Contact or 3-wire PNP
Input type Resistive
Isolation between power supply and inputs None
Isolation between inputs None
Inputs used as analog inputs( I1-I6 )
Measurement range DC 0---10V
Input impedance Min, 24KΩ ; Max. 72KΩ
Input voltage 28.8 V DC max
Resolution 10bit ,0.01V
Accuracy at 25 °C ± (Max.0.02)V
Accuracy at 55 °C ± (Max.0.04)V
Isolation between analog channel and power supply None
Cable length 10 m max.  shielded and twisted 
Output parameters:
Output No. 6 (Q1-Q6)
Output type  Relay output 
Max. Allowable Power Force(Resistive) CE: 10A,250V AC/DC30V
UL/CUL:10A,250V AC; 5A, DC28V
Electrical durability Expectancy 105 Operations at Rated Resistive Load
Mechanical life 107 Operations at No Load condition
Response time Operate Time : 15 mSec. Max.
Release Time : 10 mSec. Max.
Built-in protections Against short-circuits: None
Against overvoltages and overloads: None
Switch frequency:
Mechanism  10Hz
Resistor/light load  2Hz
Sensitive load  0.5Hz
Other parameters:
Weight Approx.400g

Program language

FBD & Ladder

 

 

Dimensions&Wiring

 

Dimensions

 

Wiring

Input/Output